Monarch NICE3000new Err04 — Overcurrent At Constant Speed: Causes and Fixes

Err04 on a Monarch NICE3000new integrated controller means excess current while the elevator runs at steady speed. It is a fault we handle regularly on NICE3000new systems overseas, and in most cases it comes from output ground fault or short circuit rather than a failed main board.

Possible Causes

  • Output ground fault or short circuit
  • Motor parameters not tuned
  • Excessive encoder interference

Step-by-Step Troubleshooting

  1. 1. Contactor check: a. Verify the run contactor on the controller output side works properly b. Verify the star-sealing contactor is not shorting the controller output
  2. 2. Motor check: a. Inspect motor cables for surface damage, possible ground fault, and loose connections b. Check the motor terminal box for copper strands touching ground, internal short or ground fault c. Verify motor U/V/W phase sequence
  3. 3. Motor parameter check: a. Verify motor parameters match the nameplate b. Repeat motor auto-tuning
  4. 4. Encoder check: verify pulses-per-revolution setting; check for interference; run encoder wiring in a separate conduit, single-point shield grounding; verify firm mounting and coupling between encoder shaft and motor shaft; check smooth operation at high speed. For induction motors, compare current in open-loop run to judge the encoder

Pro Tip From the Field

Err04 at constant speed usually points to encoder interference or a tuning issue – check the encoder loop and re-tune before assuming a bad module.


Still stuck on this fault? Our engineers repair and supply Monarch NICE3000 systems every day. Message us on WhatsApp (+86 139 8566 2489) — send a photo of your board or the fault display, and we will identify the part and guide you through the fix. Every board and part we ship is 100% run-tested before dispatch, with a 12-month warranty.